Chilled Water Systems

Lesson 4.3

What Is a Chilled Water System

The mirror image of the hot water system. The chiller replaces the boiler; the process moves heat out of the building instead of into it. The control architecture is nearly identical.

OAT lockout: Unlike a boiler, a chiller cannot run in very cold weather. Most chillers lock out below 40-50 degrees F outdoor air temperature.

Chilled water supply temperature reset: On mild days, delivering 48-54 degrees F water is sufficient and the chiller runs at better efficiency.

Point Map

Point Description Category
CHW_SupTemp Chilled Water Supply Temperature AI
OAT Outdoor Air Temperature AI
CHW_DP Loop Differential Pressure AI
Pump1_Proof Pump 1 current switch proof BI
Pump2_Proof Pump 2 current switch proof BI
VFD1_Spd Pump 1 VFD speed command 0-100% AO
VFD2_Spd Pump 2 VFD speed command 0-100% AO
Chiller_En Chiller enable relay BO
Pump1_En Pump 1 enable relay BO
Pump2_En Pump 2 enable relay BO

Software points: Sys_Enable (BV), Rotate_Pumps (BV), CHWST_SP (AV), DP_SP (AV).